The equipment manufacturer (for general or one-time approval) and end user of the equipment (for one-time approval) can apply for equipment approval.

Published:
    Read FAQ
Will I need to send a sample of the equipment for evaluation?

Yes. In all cases, you are required to provide the equipment for evaluation.

Published:
    Read FAQ
Do I need an elevator permit to install a car lift in an auto repair garage?

An elevator permit is not required for a car lift within an auto repair garage, as the Los Angeles City elevator code does not apply to car lifts per the City of Los Angeles Elevator Code Section 92.0103.

Published:
    Read FAQ
I am installing a new elevator in an existing building. Does it need to comply with the requirements for medical emergency elevators?

If the building was built prior to 1/26/1988, the elevator does not have to comply with the requirements for medical emergency elevators.

Published:
    Read FAQ
Can I install a master PRV downstream of the fire pump in a sprinkler system?

A master PRV is allowed to be installed downstream of a fire pump when a second master PRV is installed to provide redundancy, so that failure of one PRV does not affect the operation of the fire protection system.

Published:
    Read FAQ
How many sprinkler heads do I need to hydraulically calculate for a single family dwelling sprinkler system?

Maximum two residential heads shall be hydraulically calculated for the design criteria listed in section 10.2.1 of NFPA 13D.

Published:
    Read FAQ
How do I size the fire water storage tank for a high-rise building?

The fire water storage tank is sized according to the sprinkler or standpipe demand, whichever is larger for the water supply duration as stated in NFPA 13 table 11.2.3.1.2

Published:
    Read FAQ
What are the pressure and flow requirements at the standpipe hose valves?

The flow and pressure requirements are 250 GPM at 100 PSI when PRV is not required, and 250 GPM at 125 PSI when PRV is required.

Published:
    Read FAQ
What are the requirements for fire protection in a high-rise retrofit building?

Refer to section 8604.6.5 of LABC.

Published:
    Read FAQ
When do I need to have a storage tank for fire protection?

Storage tanks for fire protection are required for new high-rise buildings over 75 ft. and for existing building falling under the scope of chapter 86 of LABC when the building height exceeds 150 ft.